Running of SL USBIO 16x8 card drivers in Windows can take up to 10 minutes. To reduce this time to 2 minutes, use the utility to configure the USB device sensor/relay SL USBIO 16x8 - it can be downloaded at AxxonSoft website.
Set a lower value of the TimeOut PowerUp parameter for each device in this utility (recommended value is 10-20 seconds). The utility does not provide the ability to select a specific device, so you should connect one SL USBIO 16x8 device in turn, disconnecting others.

Intellect Axxon PSIM is to be started after running drivers of SL USBIO 16x8 devices (you can control the status of the drivers via the Windows Device Manager).

If auto start of Intellect Axxon PSIM is configured using the Auto Startup feature in Windows, then configure the delayed start of Intellect Axxon PSIM at least 2 minutes after the operating system reboots.

If Intellect Axxon PSIM starts as a Windows wrapper, safe operation of the SLIO USBIO 16x8 card is not guaranteed in Intellect Axxon PSIM. In this case, select another way to start Intellect Axxon PSIM (see  Configuring system startup and shutdown section in  Administrator's Guide).

...