By The Modbus Discrete Register, the Digital Input is meant Discret Register refers to the Digital Input. It is possible to only read the Digital the Digital Input by getting the real state of this input on sensor or device. The register size is 1 bit. |
The Modbus Discrete Discret Register is configured as follows:
- Go to the settings panel of the Modbus Discret Register object that is created on the basis of the Modbus Device object.
In the Address field (1), enter the Discret Register address in the register map of this device.
Note title Attention! - The registers map is provided by the manufacturer.
- The register address is always less than the register number by 1. The register address is specified in the settings.
Click the Read value button (3) if it is necessary to read the device register.
Info title Note The Value area (2) displays the current Discret Register value in the selected format.
- Set the Auto update checkbox (4) if it is necessary to automatically read the register values with the interval specified on the Modbus Device object settings panel.
- Set the Poll checkbox to start polling the Modbus Discret Register. This makes the settings available for editing.
- From the Rule drop-down list, select the Modbus rule to which this Discret Register complies (see From the Rule drop-down list (5), select the rule to which this Register will obey (see Configuring the Modbus Rule).
- Set the Value change checkbox (6) if it is not necessary to display the events on the register value change in the Event Viewer. Clear the Indicator change checkbox (7) if it is necessary to allow displaying the register values in the plain text on the map Skip 'value changed' event checkbox, so that the Event Viewer window doesn't display the events of Discret Register value change.
- Set the Skip indicator feature checkbox to disable the display of the Discret Register value on the map in text form.
Note title Attention! Value change Сhange of this parameter will be is applied after restarting the you restart the ACFA PSIM Server.
- Set the Config event checkbox (8) if it is not necessary to display the events in the Event Viewer when the rule is triggered. Skip rule-configured events checkbox, so that the Event Viewer window doesn't display the events of rule triggering.
- From the Interpretation drop-down list, select the Discret Register data format:
- Single Flag,
- 8 Flags (1 byte),
- 16 Flags (2 bytes).
- To add a numeric operation to the table, click the button.
Info title Note To delete a numeric operation from the table, click the button.
You can change the sequences of operations using the following buttons: to move up one position, click the button, to move down one position, click the button.
- From the list of operations, select:
- Inversion.
- Mask.
In the Mask operation settings window:- From the Mode drop-down list, select the logical operator AND (default), OR, or XOR.
- Specify the bitmask value in decimal (DEC) or hexadecimal (HEX) format, or set the corresponding checkboxes.
- Click the OK button to save the settings.
- Click the Apply button to save the settingsClick the Apply button (9) to save the changes.
The Modbus Discret Register is now configured.