To configure alarm processing in the system, do the following:
- Go to Settings → Options(1) → Alarm processing(2).
Image RemovedIn the . - Enter the required parameter settings specified in the table:
| Parameter | Value | Description |
|---|
| Alarm processing |
| Time period of operator reaction to alarm |
field (3), enter | [hours], [minutes], [seconds] | Enter the time during which |
the an alarm must be taken into processing |
, otherwise . Otherwise it is assigned the Skipped status. The |
minimum default value is 5 minutes. To change the time limit, specify a value in the range: - hours [0, 96]
- minutes [2, 59]
- seconds [0, 59]
| Note |
|---|
| Minimum time limit is 0 hours, 2 minutes, 0 seconds. |
|
is taken - into processing, the time for handling it is unlimited.
|
|
Set the maximum time for an alarm to stay on a special layout (4 |
| Time a camera is on alarm layout | [hours], [minutes], [seconds] | Enter the time during which an alarm is displayed on the alarm layout ( |
, see Working with Special layouts). After the specified time has elapsed, the alarm is removed from the layout, and its place is taken by the next alarm, which has not yet been displayed on the layout. |
By default, the time isn't set. To change the time limit, specify a value in the range: - hours [0, 96]
- minutes [2, 59]
- seconds [0, 59]
|
| Mandatory comment |
| Confirmed alarm | Image Added
| By default, when an alarm is triggered, a comment isn't provided (the checkbox is clear). If a mandatory comment is required, set the checkbox |
Image Added
|
| Suspicious situation | Image Added
| By default, when an alarm is triggered, a comment is provided (the checkbox is set). If a mandatory comment isn't required, clear the checkbox |
Image Added
|
| False alarm | Image Added
| By default, when an alarm is triggered, a comment isn't provided (the checkbox is clear). If a mandatory comment is required, set the checkbox |
Image Added
|
- Click the Apply
Image Added Select the alarm assessment, after accepting which, the operator is required to enter a comment (5).
- Click the Apply button.
Configuration of alarm processing is now complete.