Periods of collecting the data on the Agent of Control technical condition data collection periods status are given below:
- Information on disk failures (the Disk failure alarm type) and its restoring is updated in the following cases:
- at the Agent of Control startup and then every 15 minutes.
- at receiving local message SLAVE|the NO_DISC (No disk for archive storage) local message from Axxon the Axxon PSIM core.
- at receiving local message the DISC_EXIST (Disk for archive storage found) local message from the Axxon PSIM core.
- at receiving local message the DISC_UNMOUNT (Disk unmounted) local message from the Axxon PSIM core.
- at receiving local message the DISC_MOUNT (Disk mounted) local message from the Axxon PSIM core.
- Information on the archive size (the Small the small archive size alarm type) is updated at the Agent of Control startup and then every 15 minutes.
- Information on the computer's normal and abnormal restarts is displayed in the interface within 5 five minutes.
- Information on free disk space is updated every 1 hour.
The Agent of Control initiates the connection with the Server of Control and, once in a ping the polling period (2 two minutes by default), sends a package with the technical data status to the Server of Control. If the Server of Control haven doesn't been receiving receive any data package from the Agent of Control for 6 six minutes, then the "No connection" error is displayed for such object.
| Info |
|---|
|
The You can change the waiting timeout for receiving receiving the packets packages with the technical state status of the Agent of Control can be adjusted. To do this, do the following: - On the Agent of Control side, in on the settings panel of the Partition Partition of Control, add a one-character postfix to the identifier of this object (for example, if the Partition the Partition of Control has an identifier equal to 123, then the identifier with the postfix will look like looks like 123X, where X is the specified postfix).
- On the Agent of Control side, it is recommended to adjust we recommend correcting the Server of Control polling period so that it does not doesn't exceed the waiting timeout for receiving the packets packages with the Agent of Control technical condition status (see Configuring communication between Agent Of Control and Server Of Control).
- On the Server of Control side, delete the existing Partition existing Partition of Control with athe 123 identifier.
- On the Server of Control side side, create a new the new Partition of Control with a the 123X identifier.
- On the Server of Control side, for the PostfixForTimeOut parameter of the HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\BitSoft\VHOST\VHostService registry key, set the value equal to the previously specified postfix. For , and for the TimeoutForPostfix registry key parameter, set the timeout value in minutes (for details, see Registry keys reference guide, for more information about working with the registry, see Working with Windows OS registry).
|
- The videoVideo.run process status (hangup) is checked at startup of lag is checked when you start the Videosrv.exe module and then every 15 minutes, and besides thatalso each time you reconnect the Videosrv.exe module reconnects with the to Axxon PSIM software, i.e. if the Axxon PSIM software was shut down and started again. , that is, if you shut down Axxon PSIM and start it again.