Go to documentation repository
Page History
The The AIM SC reader is configured on the settings panel of the Apollo AIM SC Reader object. This object is created on the basis of the Apollo AIM SC object.
To configure the AIM SC reader, do the following:
- From the Number drop-down list (1), select the reader's address.
- Set the Activate checkbox (2) to activate theAIM SC reader.
- In the Modes group (3), configure the reader operation modes:
From the Initial drop drop-down list select the mode of reader operation while when establishing the connection establishing.
Operation mode Description Closed Access is closed for all Only card Access granted by access card PIN or card Access granted by access card or PIN code Card and PIN Access granted by access card and PIN code Opened Access is opened for all Facility code Access is granted by facility code - From the Independent drop-down, list select the mode of reader operation while losing when the connection is lost.
- Set the Use initial mode checkbox if it's required to switch to initial mode after writing of the configuration.
In the Time group (4), set the time parameters of the reader:
Parameter Parameter setting method Description Time of door closing, s Enter the value in the field Time of opening in seconds Time of door holding, s Enter the value in the field Time period in seconds during which door is to be closed. Otherwise, the Door holding message will be triggered Alternative time of door closing, s Enter the value in the field Alternative time of opening in seconds. It is in use by special command (from card, using macro or script) Alternative time of door holding, s Enter the value in the field Alternative time period in seconds during which door is to be closed. Otherwise, the Door holding message will be triggered. It is in use by special command (from card, using macro or script) In the Advanced settings group (5), set the additional reader parameters:
Parameter Parameter setting method Description Make decision on access locally Set the checkbox YesSet—the AIM module makes an access decision without the AAN central controller Warning before alarm Set the checkbox YesSet—trigger warning before alarm Entrance by two cards Set the checkbox YesSet—passage through the reader is performed by two cards Sound notification while door unblocking Set the checkbox YesSet—sound signal of reader while unblocking the door Disable second door in binding mode Set the checkbox YesSet—block the reader working for exit from secured areas Disable only bounded reader while blocking Set the checkbox YesSet—only bounded reader are blocked while locking signal
NoClear—all readers are blocked
Use "soft" APB Set the checkbox YesSet—antipassback is available, but the corresponding mistake will be specified in message Use cards buffering while passage Set the checkbox YesSet—write access cards to the AIM while passagepassing Mode of additional relay Select the value from the list Disabled—mode of additional relay is disabled
Enabled—mode of additional relay is enabled
In the Basic settings group (6), set the basic parameters of the reader:
Parameter Parameter setting method Description Allow impulse reset Set the checkbox YesSet—impulse reset enabled Do not use full time of door closing Set the checkbox YesSet—lock after door closing Do not use exit button Set the checkbox YesSet—disable exit button Use AUX as sensor of door opening Set the checkbox YesSet—use additional AUX sensor of the AIM module as sensor for door opening Do not wait for access cycle Set the checkbox Yes—passage is Set—access is performed after making an access decision
No—passage is Clear—access is performed after triggering a sensor of door opening
- In the Regions group (7):
- From the Entrance to drop-down list, select the Region object corresponding to the area on the side of exit through this reader.
From the Exit from drop-down list, select the Region object corresponding to the area on the side of entrance through this reader.
Info title Note In order to be able to select partitions, it is necessary to bind these partitions in the Matching of regions group on the settings panel of the Apollo AIM SC object (see Configuring the AIM SC controller).
- Click the Apply (8) button.
...
- .