Note

A detailed description and operating instructions for the ETHM-A module via GX Soft tool can be found on the official Satel website: ETHM-A – SATEL.

To configure minimum required settings which allow communication between Satel2 ETHM-A universal monitoring module and Axxon One, read the instructions below.

On the page:

Connecting the GX Soft tool to the Satel2 ETHM-A universal monitoring module 

To connect the GX Soft tool to the Satel2 ETHM-A universal monitoring module, do the following:

  1. Open the GX Soft tool.

    Note

    Recommended version: 2.1.5 or later.

  2. Click the + button to create a new project.
  3. From the drop-down list, select ETHM-A.
     
  4.  Click the CONNECTION button.
  5. Specify the connection method, and then select a module from the list of detected modules. If the module is not automatically detected, you can manually specify the connection settings.

If the settings are correct, you will be able to establish the connection by clicking the dedicated button on the top panel.

Preview and configuration of inputs and outputs

Input/Output preview

GX Soft tool allows you to view the status of the module's inputs and outputs in real time. You can preview the status by clicking the Input/Output states button.

Input/Output configuration

Note

Configuration of Satel2 ETHM-A inputs and outputs is not possible via Axxon One VMS; you can configure them via GX Soft tool.

In order to configure inputs and outputs of Satel2 ETHM-A universal monitoring module, please refer to the ETHM-A general information manual, available on the manufacturer's website.

Preparing connection to Axxon One server 

In order to prepare the connection between Axxon One server and Satel2 ETHM-A universal monitoring module, do the following:  

  1. Go to HARDWARE → NETWORK and set up a static IP address for the Satel2 ETHM-a universal monitoring module. It must belong to the same network as Axxon One server.


  2. Go to FUNCTIONS → COMMUNICATION, and set the Connect to GX Soft and Direct connection checkboxes to be able to establish a LAN connection to the GX Soft software.
  3. Go to FUNCTIONS → IoT and configure the settings according to the table below.

    ParameterRecommended valueDescription
    IoTEnabledEnables IoT
    Polling typeJSON/HTTPPolling type
    PortNAPort used to send data to Axxon One. Default port is 8080
    Server

    [Axxon One server IP address]

    Specifies the computer to which the universal monitoring module will send the data to
    PollingNAPolling time in DD:HH:MM:SS format
    HTTP headerPOST http://%H%:%P%/write HTTP 1.1
    User-Agent: ETHM-A %V%
    Content-Type: application/json
    HTTP header for sending events to Axxon One
    OptionsNADefines situations in which the universal monitoring module will send messages with data to Axxon One
    FrameNADefines the settings that the GX Soft software will upload to the universal monitoring module upon request